Skip to content

PROTECTING YOUR WORLD

Metal Building
Insulation: Real
R-Values & Code

What each insulation really delivers over the purlins, what the energy code asks for, and how to stop the dripping. We make ArmorFoam, and we’ll tell you when a liner system is the better call.
Metal Building Insulation

Insulating a steel building? Get a quote from a certified applicator.

Tell us the building size, the roof type and how you use it. We'll connect you with an ArmorThane-certified spray foam applicator who will quote foam type, thickness and R-value in writing.

  • Shops, warehouses and pre-engineered metal buildings
  • Sweating roofs and condensation retrofits
  • Thickness, R-value and fire barrier spelled out on the quote
  • Contractors: ask about ArmorFoam material and spray rigs
Rather talk now? Call (417) 831-5090
Step 1 of 3
≈R-6.6
What R-19 delivers over purlins
Screw-down roof, ASHRAE 90.1 App. A
45.9°F
Dew point at 65°F, 50% RH
Bare steel on a 10°F night: ≈21°F
0.82 gal
Water per gallon of propane
Burned in an unvented heater (our math)
U-0.035
Max roof U, zones 0–5
2021/2024 IECC, metal buildings

Metal building insulation has two jobs, and plenty of buildings only get one of them done. The first is slowing heat. The second is keeping warm, damp indoor air off steel that sits at nearly the outdoor temperature. Miss that one and the roof rains on your equipment every cold morning.

This guide covers both for steel and pre-engineered metal buildings (PEMBs): what each insulation type really delivers once it's crushed over a purlin, what the energy code asks for by climate zone, where spray foam works on steel and where it doesn't, and what it costs. Four interactive tools run the numbers for your building. If yours is a post-frame barn with wood girts, our pole barn insulation guide is the better fit.

A disclosure up front. We manufacture ArmorFoam closed-cell and open-cell spray foam, and we've been making foam and coatings for more than 35 years. We still think a factory liner system is the better answer on a new standing-seam building, and we'll say so wherever it applies.

The short answer

What is the best insulation for a metal building?

Quick answer

For an existing metal building with a through-fastened (screw-down) roof, closed-cell spray foam bonded to the steel is usually the best insulation: R-value, an air barrier and a vapor retarder in one layer. For a new standing-seam PEMB, a factory liner system with thermal blocks is the proven, code-compliant route. Either way, the vapor control layer has to be continuous.

The rest of the answer turns on four things: the roof (through-fastened or standing seam), new construction versus retrofit, how the building is used, and your climate zone. The table compares every common option on the numbers that matter in a steel building. Pay attention to the vapor control and air barrier columns. They decide whether the building drips.

TypeR-valueVapor controlAir barrierInstalled costBest for
Faced fiberglass blanket (NAIMA 202)R-19 blanket is 5.60 in thick; over purlins it performs like R-6.6 to R-12.2Facing, 0.02–0.09 permOnly if taped and continuous$0.80–$2.60/sq ftNew buildings on a budget
Liner system / filled cavityR-19 + R-11 LS: U-0.037 (≈R-27); R-30 + R-11: U-0.029Continuous liner below the purlinsYes, if sealedNot reliably publishedConditioned PEMBs, standing seam roofs
Closed-cell spray foamR-5 to R-7 per inch; ArmorFoam R-6.5 aged0.83 perm at 1 in (ArmorFoam)Yes, at 1 in (ASTM E2178)$1.30–$2.90 per board footRetrofits, screw-down roofs, condensation
Open-cell spray foamR-3.5 to R-3.7 per inch; ArmorFoam 0.5 R-3.9 at 1 inNone: vapor-open, 8–12 permsYes$0.60–$1.30 per board footFill over closed-cell; sound
Rigid board / continuous insulationPolyiso R-6/in; XPS R-5; EPS R-4Foil facers are low-permOnly with taped seams$1.20–$3.70/sq ftWall ci, barndominiums
Insulated metal panelsR-6 to R-8 per inchSteel skinsYes$4.00–$8.00+/sq ftNew high-performance buildings
Radiant barrier / bubble foilReflects radiant heat only; needs a 1 in air spaceFoil is low-permOnly if seams are sealed$0.50–$2.20/sq ftHot-climate add-on
R-values: HomeGuide (Dec. 2025) for spray foam ranges; ArmorThane data for ArmorFoam; Johns Manville Microlite L data sheet; Rmax (polyiso); ColoradoENERGY (XPS, EPS); MetalPro (panels). Perms: Lamtec facing data sheets and ArmorThane. Liner-system U-factors: ASHRAE 90.1-2016 Appendix A via NAIMA. Installed costs: HomeGuide (Nov. 2025), except panels (MetalPro, 2026). We didn't find a reliable published installed cost for liner systems.

The pattern is simple. Blankets and liner systems win on a new building because they go in while it's being erected. Closed-cell foam wins on an existing screw-down building because it's the one option that bonds to the steel. Foil isn't insulation on its own. For a recommendation specific to your building, jump to the system selector.

The physics

Why metal buildings need insulation (and why they sweat)

Steel conducts heat so well that an uninsulated panel sits within a few degrees of the outdoor temperature. When warm indoor air touches it, that air cools below its dew point and leaves its moisture on the steel. Insulation fixes the heat problem. Only a continuous vapor control layer fixes the dripping.

Steel runs at outdoor temperature

Here's the math for a cold night. Take a shop held at 65°F and 50% relative humidity with 10°F outside. The only things resisting heat flow through a bare steel panel are two thin films of still air, about R-0.68 on the inside and R-0.17 on the outside, using the commonly published ASHRAE values. Run those through the standard series-resistance formula and the panel sits at roughly 21°F. The dew point of that indoor air is 45.9°F. The steel is 25 degrees below it, so the underside frosts overnight, and when the sun hits the roof it rains inside.

Roofs get an extra push on clear nights. They radiate heat to the open sky, and surfaces can frost even when the air never drops below freezing. How many degrees that adds varies with the sky and the roof, so the calculator below leaves it as an optional input.

Where the moisture comes from

Every occupied building makes water vapor. People breathe it out, concrete slabs give it off, and trucks and equipment roll in wet. Livestock add a lot. The one owners tend to overlook is the heater. Burning propane makes water, and an unvented propane or kerosene heater puts all of it into the room. By our math from the combustion chemistry, every gallon of propane burned releases about 0.82 gallon (6.9 lb) of water vapor. Run a torpedo heater through 5 gallons in a day and you've added about 4 gallons of water to the air.

Energy, comfort and rain noise

Energy savings are real, though the only broad figure we'd quote is for homes: ENERGY STAR says sealing air leaks and adding insulation can bring "up to a 10% savings on your annual energy bills." Comfort is the more obvious change, since you're no longer working under a sheet of steel at outdoor temperature. Noise counts too. Rain on a bare metal roof is loud, and insulation soaks up a good share of it. Johns Manville's faced metal building blanket at R-19 has a noise reduction coefficient (NRC) of 0.85–0.90 on ASTM C423, and 1.10 unfaced. More in does spray foam reduce noise.

Know your options

Metal building insulation types compared

There are seven common ways to insulate a steel building: faced fiberglass blankets, liner systems, closed-cell spray foam, open-cell spray foam, rigid board, insulated metal panels and radiant foils. They differ less in R-value per inch than in how they handle the purlins, the vapor and the air, and that's where metal buildings fail.

Faced fiberglass blankets (NAIMA 202)

This is what most PEMBs ship with: a roll of fiberglass laminated to a facing, pulled over the purlins or girts before the panels go on. Johns Manville's Microlite L is a typical example. It's certified to NAIMA 202-96, meets ASTM C991 Type 1, lists an ASTM E84 flame spread of 25 or less and smoke developed of 50 or less, and comes in 36- to 72-inch widths. After lamination, R-10 is 2.95 inches thick, R-13 is 3.85, R-19 is 5.60, R-25 is 7.50 and R-30 is 8.70.

The facing is the vapor control, so choose it on purpose. Here's what one facing maker publishes:

Lamtec facingConstructionPerm (ASTM E96)Flame / smoke (E84)BurstRated for
WMP-VRPolypropylene / scrim / kraft≤0.0910 / 1060 psiLow-cost standard duty
WMP-10Metallized PP / scrim / kraft≤0.0210 / 1065 psiStandard duty
WMP-30UL-classified OEM PSK≤0.025 / 570 psiHeavy duty
WMP-50PP / scrim / core / metallized polyester≤0.025 / 30120 psiPremium heavy duty
GymguardPP / fiberglass-polyester fabric≤0.020 / 30250 psiHighly abuse resistant
All five are Class I vapor retarders (0.1 perm or less) under Building Science Corporation's classes. A retail VRR+ facing is listed at under 0.02 perm (Insulation4less). No facing works if its seams and tabs aren't sealed.

The catch is the purlins. A single layer draped over them gets squashed to almost nothing at every one, and the next section shows what that costs. Sag-and-bag and double-layer systems add a second blanket between the purlins to win some of it back. Building makers sell these under their own names; Nucor, for one, lists single-layer faced roofs from R-8 to R-38, sag-and-bag at R-26 to R-35, long tab and banding at R-30 to R-44, and liner systems up to R-53.

Liner systems, filled cavity and long tab banded

A liner system (LS) turns the approach upside down. The code describes it as a vapor-retarder membrane run continuously below the purlins, not interrupted by framing, with unfaced insulation laid uncompressed on top of it between the purlins. The insulation keeps its full thickness and the vapor retarder runs unbroken under the steel. It's also the form the IECC's prescriptive roof values for metal buildings take (see the code table). Filled cavity (FC) and long tab banded systems are related ways of getting more uncompressed fiberglass between the purlins. Where a design uses thermal spacer blocks on the purlins, ASHRAE 90.1-2022 assumes R-3 blocks for most assemblies and R-5 for the filled cavity. All of these systems go in during erection.

Closed-cell spray foam

Closed-cell spray polyurethane foam (SPF) is sprayed as a liquid and bonds directly to the steel. Published R-values run R-5 to R-7 per inch depending on the product; ArmorFoam closed-cell is rated R-6.5 per inch aged (ASTM C518), with a 1.9 lb/ft³ core density and 92–96% closed cells. ASTM C1029, the specification for this kind of foam, covers service surfaces from −22°F to +225°F.

What sets it apart in a metal building is everything else it does. At 1 inch, ArmorFoam closed-cell measures 0.83 perms (ASTM E96) and qualifies as an air barrier under ASTM E2178. It covers the purlins and girts instead of being crushed by them, and it leaves no gap for air to reach the steel. That's why it's the default for retrofits and sweating roofs, with exceptions covered in the spray foam section. Our closed-cell spray foam guide has the full spec sheet, and the spray foam R-value chart and calculator converts inches to R.

Open-cell spray foam (and why it's not a vapor retarder)

Open-cell foam is light, cheaper per board foot and good at soaking up sound. ArmorFoam 0.5 is a water-blown 0.5 lb/ft³ foam rated R-3.9 at 1 inch and R-13.6 at 3.5 inches (ASTM C518); generic open-cell runs R-3.5 to R-3.7 per inch. It stops air, but it's vapor-open: 8–12 perms in our own data. In a heated building in a cold climate, vapor moves right through it to the cold steel. So on steel, we treat open-cell as a fill layer over closed-cell, never the layer that touches the metal. The open-cell spray foam guide covers where it shines.

Rigid board and continuous insulation

Polyiso, XPS and EPS boards run about R-6, R-5 and R-4 per inch. Installed across the framing, board becomes continuous insulation (ci), which the code defines as insulation running uncompressed across all structural members, with no thermal bridges other than fasteners and service openings. Compressed fiberglass doesn't count. Board shows up most often as the ci layer on walls and in barndominiums. Foil facers are low-perm, but every seam needs tape before the board works as an air barrier.

Insulated metal panels

Insulated metal panels (IMPs) are foam cores bonded between two steel skins, installed as the wall or roof itself. MetalPro lists them at about R-6 to R-8 per inch and $4.00 to $8.00+ per square foot installed. They're a new-construction product for high-performance buildings, not a retrofit.

Radiant barriers and bubble foil: what they can and can't do

A radiant barrier reflects radiant heat. It doesn't slow conduction the way insulation does, and it only works when "the reflective surface must face an air space," which the Department of Energy puts at 1 inch or more. Dust on the foil cuts the effect. DOE reports 5–10% cooling cost reductions in warm, sunny climates. So foil can be a sensible add-on in the South, but foil pressed tight to the steel loses the air space it depends on. One horse-barn owner on the TractorByNet forum called his "worse than worthless."

Interactive tool 1 of 4

Nominal R-value vs real R-value over purlins

The R-value printed on a blanket describes the blanket, not the roof. Draped over purlins, it's crushed to a fraction of its thickness at every one, and the steel carries heat around it. ASHRAE 90.1 rates R-19 over a through-fastened roof at U-0.151. That's about R-6.6 for the whole assembly, roughly a third of the label.

Those numbers come from ASHRAE 90.1-2016 Appendix A, the assembly tables used for metal building compliance, as reproduced in NAIMA's compliance guide. U-factor is the heat flow through the whole assembly with framing and air films included, and effective R is simply 1/U. These rows tell the story:

SystemRoofRated RU-factorEffective R
Single layer R-19Through-fastenedR-190.151R-6.6
Single layer R-19Standing seam, thermal blocksR-190.082R-12.2
Double layer R-19 + R-19Standing seam, thermal blocksR-380.060R-16.7
Single layer R-19 + R-13 ciStanding seam, thermal blocksR-320.040R-25.0
Liner system R-19 + R-11Standing seam, no blocksR-300.040R-25.0
Liner system R-19 + R-11Standing seam, thermal blocksR-300.037R-27.0
Long tab banded R-19 + R-11Standing seamR-300.037R-27.0
Liner system R-25 + R-16Through-fastenedR-410.042R-23.8
Liner system R-30 + R-11Standing seam, thermal blocksR-410.029R-34.5
Liner system R-25 + R-11 + R-11Standing seam, thermal blocksR-470.026R-38.5
U in Btu/h·ft²·°F from ASHRAE 90.1-2016 Appendix A via the NAIMA guide. Effective R = 1/U (our arithmetic) and includes the inside and outside air films, about R-0.85 together. Click a header to sort.

Two things jump out. A single layer never gets close to a modern code roof on its own, and the same blanket performs almost twice as well under a standing seam roof with blocks as it does under a screw-down roof. The history matters too. Older ASHRAE 90.1-2001 tables credited R-19 under a standing seam roof with U-0.065 (about R-15.4). In January 2010, ASHRAE acknowledged that its 1999 through 2007 values for over-purlin, over-girt and sag-and-bag assemblies "do not reflect the performance of these assemblies as they are typically installed." If an old spec sheet or energy calc looks generous, check its date.

One more nuance. The IECC's prescriptive R-value path for zones 0–5 lists R-19 plus an R-11 liner system, while the U-factor path caps the roof at U-0.035. Appendix A gives that same liner system U-0.037 with thermal blocks, a hair over. The two paths aren't interchangeable. Pick one, and document it in DOE's COMcheck rather than mixing them.

Real R-value checker

What does your roof insulation really deliver, and does it meet code?

U-factors from ASHRAE 90.1-2016 Appendix A (via NAIMA). Zone limits are the 2021/2024 IECC metal building roof values as reproduced by Thermal Design and Bay Insulation. Verify against the code your jurisdiction adopted.

ArmorFoam closed-cell: R-6.5 aged
U-0.151
Assembly U-factor
R-6.6
Effective R (1/U)
30%
Of the label R delivered
U-0.035
Zone max roof U

Fails U-path Single layer R-19 on a through-fastened roof rates U-0.151, about R-6.6 for the whole assembly, against a zone 4 maximum of U-0.035. It delivers 30% of its rated R-19 (air films excluded). Zone 4 prescriptive roof: R-19 + R-11 LS (max U-0.035). Walls: R-13 + R-13 ci (max U-0.052).

Single layer

A single layer fails every zone’s roof limit

Even with R-13 continuous insulation added, the best single-layer row here is U-0.040. Compressed over the purlins, the blanket can’t reach code on its own. Look at liner systems, or at double layers with ci.

Retrofit option

Existing screw-down roof?

Closed-cell foam bonded to the panels covers the purlins instead of being crushed by them. Switch the system to “Closed-cell spray foam” for a nominal comparison.

Walls follow the same logic. Appendix A lists a single-layer R-25 wall at U-0.059 and R-30 at U-0.052, each with a thermal spacer strip when there's no continuous insulation. R-25 covers the zone 0–3 wall limit of U-0.079, and R-30 just reaches zone 4's U-0.052. From zone 5 up, the walls need continuous insulation, which is why every prescriptive wall value in the code table includes ci.

Interactive tool 2 of 4

How to stop condensation in a metal building

Condensation stops when moist indoor air can't reach steel that's colder than its dew point. That takes three things: enough insulation that the inside surface stays warm, a continuous vapor control layer at the steel (adhered closed-cell foam or a sealed Class I facing), and less moisture in the air to begin with.

Dew point in plain English

Dew point is the temperature at which air, as it cools, can no longer hold its water vapor. Warmer, wetter air has a higher dew point. Any surface colder than that collects water, and on most winter nights bare steel is well below it. The calculator uses the Magnus formula with the coefficients published by Lawrence (2005). A few reference points:

Indoor airDew pointWhat it means
65°F, 50% RH45.9°FHeated shop, moderate humidity
65°F, 60% RH50.8°FSame shop, damper air
55°F, 70% RH45.4°FLightly heated, damp building
50°F, 80% RH44.1°FCool, humid air
Our calculation: Magnus formula, b = 17.625, c = 243.04 °C. A quick rule in Celsius: dew point ≈ temperature − (100 − RH) ÷ 5, good to about 1 °C above 50% RH.

The vapor control layer: facings, sealed seams, adhered foam

You can't keep the steel warm, because it's outboard of all the insulation. So the job is keeping indoor air and vapor away from it. There are two dependable ways:

  • Closed-cell foam bonded to the steel. At 1 inch or more it's an air barrier, and ArmorFoam closed-cell measures 0.83 perms at 1 inch, a Class II vapor retarder. Because it's bonded, there's no air space against the metal. It has to cover the purlins and girts too.
  • A faced blanket with a Class I facing, sealed. Class I means 0.1 perm or less; the facings in the table above run 0.02 to 0.09. The facing only works if every seam, tab and penetration is taped or sealed. A seam that's stapled with a gap is a path straight to the steel.

Then come the details that get skipped: closure strips at eaves and ridges, sealed daylight gaps, and sealed pipe and conduit penetrations. And the point we'd underline: open-cell foam on its own isn't a vapor control layer. At 8–12 perms it lets vapor through to the steel in a heated building.

Ventilation and moisture sources

A tighter building needs a plan for the moisture made inside it. Vent combustion heaters outside or use vented units, since an unvented heater adds about 0.82 gallon of water for every gallon of propane. Exhaust moisture where it's made, such as wash bays and animal areas. And give a sealed building fresh air; Hansen Pole Buildings calls a fresh-air intake mandatory after foaming an all-steel building.

Condensation checker

Will your metal building sweat?

A steady-state estimate using air films of R-0.68 inside and R-0.17 outside. Blanket options use ASHRAE whole-assembly U-factors, so the crushed spots at each purlin run colder than shown.

Optional. Clear-night values vary; no published default.
At R-3.7 per inch
45.9°F
Indoor dew point
21.0°F
Inside surface temp
21.0°F
Steel temp
R-1.1
Assembly R to keep surface dry
Surface condensation

The inside surface will be wet

The room-side surface runs at 21.0°F, below the 45.9°F dew point. You need at least R-1.1 of assembly R to keep that surface dry at these conditions (our calculation). You have R-0.0.

Below dew point

Your steel is below dew point. Any air or vapor that reaches it will condense.

  • Closed-cell foam fully adhered to the steel, at least 1 in (0.83 perm at 1 in, Class II), covering purlins and girts, with no liner or air gap; or
  • a faced blanket with a Class I facing (0.1 perm or less; WMP-10/30/50 are 0.02 or less), with every seam and tab sealed;
  • plus closure strips and sealed penetrations.
Honest trade-offs

Spray foam on metal buildings: what works and what doesn't

Spray foam is the best retrofit insulation for most through-fastened metal buildings, and the wrong choice for standing seam roof panels. It works when closed-cell foam goes on clean, dry steel, fully bonded, covering the framing, and then gets protected the way the fire code requires. Most of the spray foam horror stories trace back to skipping one of those steps.

Through-fastened vs standing seam roofs

Industry guidance summarized from SPFA and the Metal Construction Association says SPF is suitable below and in contact with through-fastened metal roofs, the screw-down R-panel and PBR roofs on most shops. It discourages SPF in contact with standing seam roofs designed for thermal expansion and contraction, because bonded foam can restrict that movement. Therm-All's guide gives the same warning.

On a standing seam building, insulate the roof with a liner system or on a separate substrate, and use foam on the walls. Rmax adds that PEMB manufacturers often don't allow foam sprayed directly on their panels, so read the building and panel warranties before you book a sprayer.

Closed-cell spray foam covering the girts and wall panels inside a metal building
Spray foam on the walls of a metal building. It covers the girts as well as the panels.

Will spray foam rust a metal building?

Rust needs water. The failures installers describe come from a few places: foam sprayed onto steel that was wet or already rusting, condensation forming on cold metal while warm closed-cell foam is being sprayed onto it, and plastic liners or release fabrics that leave an air space between the foam and the panel. Roof leaks that feed water behind the foam are another. The fixes follow directly. Treat existing rust, fix leaks first (our metal roof coatings guide covers that), spray only dry steel, apply in several thin passes, and never spray over a liner.

Field reports are mixed, and you should hear both sides. On the Garage Journal forum, one erector reported rust-through of sheeting and secondary members 5 to 10 years after foaming and said manufacturers void warranties over it. Other owners in the same discussions report five-plus years without trouble. Those are anecdotes, not data. Treat them as a reason to get the prep right.

Thickness: flash coat, full fill and flash-and-fill

For condensation control alone, 1 inch of closed-cell is the practical floor. That's where ArmorFoam closed-cell becomes an air barrier and measures 0.83 perms. Heated shops commonly get 2 inches on all the steel.

Hansen Pole Buildings publishes a recipe for an all-steel building: seal the closures and daylight gaps, spray 2 inches of closed-cell on all walls and the roof so every bit of steel is covered, then add open-cell at 5.5 inches on the roof and 3.5 on the walls. Hansen puts that at R-33+ for the roof and R-26 for the walls, and our math agrees (R-6.5 closed-cell plus R-3.7 open-cell gives R-33.4 and R-26.0). Start with a "picture frame" pass of at least half an inch around the panel edges, as industry guidance recommends. In a cold climate, check the split between the two foams too: if the open-cell is thick relative to the closed-cell, the face of the closed-cell layer runs colder. The condensation checker shows that temperature.

Hitting a commercial code roof with foam alone takes more. On a nominal basis, reaching U-0.035 needs about 4.3 inches at R-6.5 per inch, or 5.5 inches at R-5 (our calculation). Purlins still bridge heat through the foam, and Appendix A has no pre-calculated values for foam on panels, so treat that as a planning number rather than a compliance value.

Oil canning, hail and warranties

Three more things to settle before anyone sprays. Thin panels: the same industry guidance warns that oil canning may show up on 29-gauge or thinner steel, and that foam can reach core temperatures up to 325°F for short periods as it cures. Hail: once closed-cell foam is bonded, FoamBid notes, it "cannot be separated from the substrate without destruction." Replacing a hail-dented panel means cutting out foam and re-spraying, which an insurance claim may not anticipate. Finish all roofing and siding work first, and write re-foam costs into the contract. Warranties: check the building's and the panel maker's terms, as above.

Fire code: thermal barriers, ignition barriers and intumescent coatings

Spray foam is a foam plastic, and building codes treat it that way. The IBC (Section 2603.4) and the IRC (R316.4 in the 2021 edition, renumbered R303.4 in 2024) require it to be separated from the interior by a thermal barrier. In the IRC, that's at least half-inch gypsum wallboard or a material that meets NFPA 275. A Class A flame spread rating under ASTM E84 does not satisfy the thermal barrier requirement. ArmorFoam, for example, is listed with a flame spread under 75, and our R-value guide notes it requires a thermal barrier.

The usual alternative for exposed foam in a shop is an intumescent coating evaluated for the job. ICC-ES report ESR-3702, for DC315, allows the coating over the spray foams listed in its Table 1 without the thermal barrier prescribed in IBC 2603.4 and 2024 IRC R303.4. The required thickness depends on the foam brand (9 mils dry / 14 mils wet for some, 12 dry / 18 wet for others), and it can't be applied below 50°F, above 90°F or above 85% relative humidity. The key word is listed: the coating is only valid over the foams named in the report. Ask your applicator which foam and coating they're pairing and for the report number. The IBC also has narrow exceptions and special-approval routes; confirm with your building official before you plan on leaving foam exposed. For residential work, our closed-cell guide has a fire code checker.

Why installer certification and pull tests matter

Most of what goes wrong with foam on steel is workmanship: wet substrate, thick single passes, missed purlin flanges. The industry guidance cited here recommends installers certified through SPFA's Professional Certification Program, adhesion checks with an ASTM D4541 pull tester, and a call to the panel manufacturer before work starts. Ask for all three.

Energy code

What R-value does a metal building need? Energy code by climate zone

For a conditioned commercial metal building, published reproductions of the 2021 and 2024 IECC tables put the roof at R-19 plus an R-11 liner system (or a maximum U-0.035) in climate zones 0–5, rising in colder zones, and the walls at R-13 plus continuous insulation. Living space follows the residential code instead. Unheated storage may not be covered at all.

Commercial metal buildings (IECC)

These are the metal building rows for the "all other" occupancy group, from Tables C402.1.3 and C402.1.4 in the 2021 IECC and C402.1.2 and C402.1.3 in 2024. We took them from two manufacturer reproductions, Bay Insulation and Thermal Design, which agree with each other. Check them against the edition your jurisdiction has adopted before you order a building.

Climate zoneRoof max URoof, prescriptive RWall max UWall, prescriptive R
0–30.035R-19 + R-11 LS0.079R-13 + R-6.5 ci
40.035R-19 + R-11 LS0.052R-13 + R-13 ci
50.035R-19 + R-11 LS0.050R-13 + R-14 ci
60.031R-25 + R-11 LS0.050R-13 + R-14 ci
70.029R-30 + R-11 LS0.044R-13 + R-17 ci
80.026R-25 + R-11 + R-11 LS0.039R-13 + R-19.5 ci
LS = liner system; ci = continuous insulation; U in Btu/h·ft²·°F. Per Thermal Design's reading of the 2024 IECC footnote, the R-value method requires a thermal spacer block; otherwise use the U-factor method. Local adoption and amendments vary.

Dalkita's worked example for zone 5 reads the table the same way: a roof of R-19 plus an R-11 liner system or U-0.035 or lower, and walls of R-13 plus R-14 continuous insulation or U-0.050 or lower. Remember that compressed fiberglass never counts as the ci.

Unheated and low-energy buildings

Energy codes are written around conditioned space. An unheated equipment or storage building may fall outside the envelope insulation requirements entirely, and very lightly heated buildings may be treated differently. We haven't reproduced those provisions here because we couldn't verify the current text, so ask your building official before assuming either way. Condensation control is still worth paying for where the code asks for nothing.

Barndominiums and living space

A steel building someone lives in is a house under the code, so the residential tables apply. The 2021 IECC and IRC minimums, via PNNL:

ZoneCeilingWood-frame wallFloor
1R-30R-13, or R-0 + R-10 ciR-13
2R-49R-13, or R-0 + R-10 ciR-13
3R-49R-20, R-13 + R-5 ci, or R-0 + R-15 ciR-19
4 (except Marine)R-60R-30, R-20 + R-5 ci, R-13 + R-10 ci, or R-0 + R-20 ciR-19
5 and Marine 4R-60Same as zone 4R-30
6R-60Same as zone 4R-30
7–8R-60Same as zone 4R-38
2021 IECC/IRC prescriptive minimums as summarized by PNNL's Building America Solution Center. Wall values are for wood framing.

Steel-framed walls have their own, higher equivalents in IECC R402.2.6 (IRC N1102.2.6). Look them up in the code itself rather than borrowing the wood numbers. The bigger design rule comes from building science: insulation between steel framing members does little, because the steel bridges around it. Put the insulation fully inside or fully outside the steel. On GreenBuildingAdvisor, Martin Holladay makes exactly that point, and a builder near Ottawa describes condensation on drywall along steel members where fiberglass sat between steel studs. For a barndominium that usually means closed-cell foam against the steel shell, a framed interior wall, drywall as the thermal barrier, and mechanical ventilation.

Proving compliance: COMcheck

For commercial buildings, run DOE's COMcheck to document energy code compliance, and do it before you order the building package. Swapping a single-layer roof for a liner system is easy on paper and impossible once the panels are on. The real R-value checker above is a quick screen, not a substitute.

Step by step

How to insulate a metal building

On a new building, insulation goes in during erection: faced blankets or a liner system at the purlins, with thermal blocks and sealed facings, before the panels close it in. On an existing building, the order is fix the water, seal the gaps, prep the steel, spray closed-cell foam, then protect and ventilate.

New construction

  • Decide the compliance path first. If the building will be conditioned, run COMcheck with the insulation package before you order.
  • Order the insulation with the building. Blanket and liner systems are cheapest and best installed during erection, because the roof panels go on over them.
  • Use thermal spacer blocks on the purlins where the design calls for them. The 2024 IECC R-value path requires them.
  • Pick the facing on purpose. Class I for any heated building; an abuse-resistant facing such as Gymguard or WMP-50 where equipment or animals will rub it.
  • Seal every seam and tab, and install closure strips at eaves and ridge.
  • Planning spray foam instead? Check the panel warranty, keep foam off standing seam roof panels, and schedule it after all roofing and siding work is done.

Retrofitting an existing building

  1. Find and fix the water

    Inspect the roof for leaks, loose fasteners and rust. Foam over an active leak hides it and holds water against the steel. If the roof needs work, do it first; our metal roof waterproofing page covers coating options.

  2. Check the roof type and the warranty

    Standing seam roof panels don't get foam. Through-fastened panels usually can, if the building and panel warranties allow it.

  3. Seal closures and daylight gaps

    Close the gaps at eaves, ridges and wall bases so the foam isn't the only thing stopping air, as Hansen's recipe starts.

  4. Clean, dry and treat the steel

    Remove dirt and oil, treat rust, and don't spray steel that's wet or cold enough to collect condensation. Winter work has its own rules; see applying spray foam in cold weather.

  5. Spray closed-cell in thin passes

    Picture-frame the edges first (at least half an inch), then cover panels, purlins and girts completely. No liners or release fabrics behind the foam. Spot-check adhesion with a pull test.

  6. Add fill if you want more R

    Open-cell over the closed-cell adds R-value at a lower cost per board foot. Keep enough closed-cell that its face stays above the dew point in your climate.

  7. Protect the foam

    Cover exposed foam with an approved thermal barrier or a listed intumescent coating. In animal buildings, add a cleanable covering; birds and rodents pick at bare foam.

  8. Ventilate

    Vent heaters outside and give the building fresh air. A tight building holds whatever moisture you make in it.

Interactive tool 3 of 4

Which metal building insulation system fits your building?

Match the system to the roof, the project and the use. New standing-seam building: liner system. Existing screw-down building: closed-cell foam on the steel. Unheated storage: the least that stops the drip. Barndominium: a house-style envelope inside the steel. The selector ranks the options for your case and flags the code, warranty and fire issues.

System selector

Get a ranked recommendation for your building

Rules follow the sources on this page: SPFA/MCA guidance on foam and roof type, IECC metal building values, and ArmorThane product data. It's a starting point for a conversation with your applicator or designer.

Hail-prone area?
Closed-cell spray foam on the steel, open-cell fill optionalTop pick
Best fit

1. Closed-cell spray foam on the steel, open-cell fill optional

Bonded to the panels, it covers the purlins and girts instead of being crushed by them and leaves no air space at the steel. At 1 in, ArmorFoam closed-cell is an air barrier (ASTM E2178) and measures 0.83 perms.

  • 2 in of closed-cell on all steel is common for heated shops; open-cell fill on top adds R-value.
  • Fix leaks and treat rust first. Spray clean, dry steel in thin passes, with no liners or fabric behind the foam.
  • Cover purlins and girts completely; spot-check adhesion with an ASTM D4541 pull test.
Also consider

2. Faced blanket (only if the panels are coming off)

Blanket goes between the framing and the panels, so on an existing building it only makes sense during a re-roof or re-side.

  • A single layer over the purlins performs far below its label: R-19 rates about R-6.6 under a through-fastened roof and R-12.2 under standing seam with blocks.
  • Facing: Class I (0.1 perm or less), with every seam and tab taped or sealed.
Before you buy

What to settle first

  • Warranty: check your building and panel warranties before foam goes on the steel. PEMB makers often don’t allow it (Rmax).
  • Exposed foam: the IBC (2603.4) and IRC call for a thermal barrier. The alternative is an intumescent coating listed for your specific foam in an ICC-ES report, such as ESR-3702.
  • Before anything: fix leaks and rust. Foam over a leak hides it and holds water against the steel.

Recipes by building type

BuildingUsual best choiceWatch for
Unheated storage with a dripping roofAbout 1 in of closed-cell on the steel, or a Class I faced blanket with sealed seamsCode may not require insulation; condensation control still pays
Occasionally heated shop, screw-down roof2 in of closed-cell on all steel; open-cell fill optionalVent the heater; thermal barrier or listed coating if exposed
New conditioned shop, office or warehouseLiner system roof with thermal blocks; R-13 + ci wallsRun COMcheck; don't mix the R-value and U-factor paths
Standing-seam PEMBLiner system or filled cavity; foam on the walls onlyNo spray foam against the roof panels
BarndominiumClosed-cell against the steel, framed interior walls, drywallResidential R-values; mechanical ventilation
Livestock or ag buildingClosed-cell plus a cleanable, protective covering, or a Gymguard or WMP-50 faced blanketBirds and rodents pick at exposed foam; high humidity
Existing building that sweatsFix leaks, seal closures, then 1–2 in of closed-cell covering purlins and girtsRust prep; no liners behind foam; panel warranty
Our recommendations, drawn from the sources cited on this page. Your applicator or building designer should confirm them for your building.
Interactive tool 4 of 4

How much does metal building insulation cost?

HomeGuide (November 2025) puts pole barn and metal building insulation at $1.00–$4.50 per square foot installed, or $3,500–$16,500 on average. Closed-cell spray foam runs $1.30–$2.90 per board foot and open-cell $0.60–$1.30. Faced blankets and rolls run $0.80–$2.60 per square foot installed.

Building sizeInstalled range (HomeGuide, Nov. 2025)
30 x 40$2,600–$13,500
30 x 50$3,100–$15,800
40 x 60$4,500–$22,100
50 x 100$8,200–$39,600
Insulation typeHomeGuide (Nov. 2025), per sq ftMetalPro (2026), per sq ft
Spray foam$1.00–$4.50Open-cell $1.50–$2.50; closed-cell $2.50–$5.00
Fiberglass batts and rolls$0.80–$2.60$0.50–$1.50
Foam board / rigid$1.20–$3.70$1.00–$2.50
Blown-in$0.90–$2.40–
Reflective$0.50–$2.20$0.30–$1.00
Insulated metal panels–$4.00–$8.00+
Third-party installed estimates, not quotes. For material alone, LTH Steel Structures lists faced metal building blanket at $1.46–$5.83 per sq ft depending on R-value and facing grade (Sept. 2026).

What moves the number: thickness (for foam, every added inch is another board foot per square foot), wall height and openings, access, and extras. Two extras catch people. Removing old insulation runs about $1.00–$2.50 per square foot (HomeGuide), and when foam is going onto the steel, the old blanket has to come out first. And the thermal or ignition barrier is, as our closed-cell guide puts it, frequently omitted from initial quotes. For deeper pricing and a quote checker, see our spray foam insulation cost guide.

Insulation estimator

Square footage, materials and installed cost for your building

Installed prices are HomeGuide's November 2025 ranges and already include labor. Waste only changes how much material to order. Thermal or ignition barrier not included.

Leave at 0 unless the insulation runs past the walls
ArmorFoam closed-cell: R-6.5 aged
ArmorFoam 0.5: R-3.9 at 1 in
4,966
Net sq ft to insulate
9,932
Board feet installed
R-13.0
Nominal R-value
$12,900–$28,800
Installed estimate
SurfaceAmountStatus
Roof (slope x1.0035)2,408 sq ftIncluded
Sidewalls (2)1,680 sq ftIncluded
Endwalls (2)1,187 sq ftIncluded
Doors and windows−309 sq ftSubtracted
Closed-cell 2.0 in9,932 bd ft11,422 to order (≈2.3 sets)
Net area to insulate4,966 sq ft

Board feet = square feet x inches. Installed cost uses HomeGuide’s $1.30–$2.90 per board foot for closed-cell and $0.60–$1.30 for open-cell. Sets assume about 5,000 bd ft of closed-cell per set (ArmorThane figure) plus 15% waste. For comparison, HomeGuide’s published range for a 40 x 60 (all insulation types) is $4,500–$22,100. Estimates, not quotes. Thermal or ignition barrier and old-insulation removal ($1.00–$2.50/sq ft) are not included.
Take these numbers to a certified ArmorThane applicator for a real quote.

From the manufacturer

ArmorFoam for metal buildings

We make the foam and build the rigs it's sprayed with. For steel buildings the lineup is short: closed-cell for the layer against the steel, open-cell for fill, and Roof 200 when the better answer is insulating the roof from the outside.

Roof 200 is closed-cell SPF roofing at 2.5 to 3.0 lb/ft³ for low-slope, pitched and barrel roofs, with metal among its listed substrates. It meets UL 790 as part of Class A and Class B coated roof systems, and warranties of 10, 15 or 20 years are available through approved applicators. On a standing seam building where foam can't go underneath, that's worth a look. See spray foam roofing and the Roof 200 product page. Where foam needs a tough, cleanable skin, our metal coating guide covers polyurea topcoats over SPF.

Interior of an ArmorThane mobile spray foam rig with proportioners and heated hoses
Inside an ArmorThane spray foam rig: proportioners and heated hose.
R-6.5 / in

ArmorFoam closed-cell

Aged R-value per inch (ASTM C518), 1.9 lb/ft³ core, 0.83 perms and an air barrier at 1 inch. The layer that goes against the steel.

R-3.9 at 1 in

ArmorFoam 0.5 open-cell

Water-blown, 0.5 lb/ft³, R-13.6 at 3.5 inches. Fill over closed-cell and sound control, not a vapor retarder.

UL 790

ArmorFoam Roof 200

Closed-cell SPF roofing for metal and other roofs, part of Class A and Class B coated roof systems.

ArmorFoam is sold through independent, certified applicators, and we have applicators in nearly every state. Ask any of them for the foam type, thickness, R-value and fire barrier in writing.

For contractors

Steel buildings are big foam jobs. Add them to your rig.

Shops, warehouses and ag buildings are large, repeatable closed-cell jobs, and condensation gives owners a clear reason to call. We supply ArmorFoam, build the spray rigs and train your crew. No franchise fee, no royalties, and starter packages from $25,000.

Straight answers

Metal building insulation FAQ

What is the best insulation for a metal building?

It depends on the roof and whether the building is new or existing. On an existing building with a through-fastened (screw-down) roof, closed-cell spray foam bonded to the steel gives you insulation, an air barrier and a vapor retarder in one layer; ArmorFoam closed-cell tests at 0.83 perms at 1 inch. On a new standing-seam building, a liner system with thermal blocks is the code-proven route, because spray foam shouldn't be bonded to standing seam panels.

How do I stop my metal building from sweating?

Keep humid indoor air away from the steel, which runs close to outdoor temperature. At 65°F and 50% relative humidity the dew point is about 46°F, so on a 10°F night bare steel (about 21°F by our math) condenses or frosts. Use fully adhered closed-cell foam or a faced blanket with a Class I facing (0.1 perm or less) and every seam sealed, and vent combustion heaters: an unvented propane heater adds about 0.8 gallon of water per gallon burned. Try the condensation checker.

What R-value do I need for a metal building?

For conditioned commercial metal buildings, published reproductions of the 2021 and 2024 IECC tables list the roof at R-19 plus an R-11 liner system in climate zones 0–5 (or a maximum U-0.035), rising to R-30 plus R-11 LS in zone 7, and walls at R-13 plus R-6.5 to R-19.5 of continuous insulation. A metal building used as a home follows the residential code instead, such as R-60 ceilings in zones 4–8 under the 2021 IECC. Confirm the edition your jurisdiction adopted.

Why doesn't R-19 fiberglass perform like R-19 in a metal building?

It gets crushed where it drapes over the purlins and girts, and the steel carries heat around it. ASHRAE 90.1 Appendix A rates R-19 over a through-fastened roof at U-0.151, roughly R-6.6 for the whole assembly, and about R-12.2 under a standing seam roof with thermal blocks. Check your own roof with the real R-value checker.

Can you spray foam directly on metal? Will it rust?

Yes, on clean, dry, through-fastened panels, as long as your building and panel warranties allow it. Fully bonded closed-cell foam leaves no air space where moisture can collect. Rust problems trace back to foam sprayed over wet or rusty steel, over a plastic liner, or behind roof leaks, so fix the leaks and treat the rust first.

Open-cell or closed-cell spray foam for a metal building?

Closed-cell goes against the steel. Open-cell is vapor-open (8–12 perms in our own data), so on its own it lets vapor reach cold steel in a heated building. A common approach is about 2 inches of closed-cell covering all the steel, then open-cell fill for extra R-value.

Can you spray foam under a standing seam roof?

Industry guidance discourages spraying foam in contact with standing seam panels, because bonded foam can restrict the thermal movement those roofs are designed for. Use a liner system with thermal blocks or insulate on a separate substrate, and keep the spray foam to the walls.

How thick should spray foam be on a metal building?

For condensation control, 1 inch of closed-cell is the practical minimum; that's where ArmorFoam closed-cell qualifies as an air barrier (ASTM E2178) and tests at 0.83 perms. Heated shops commonly get 2 inches. Code-level R-values take more: our nominal math puts a U-0.035 roof at about 4.3 inches at R-6.5 per inch, or 5.5 inches at R-5. That isn't a compliance value, so confirm it in COMcheck.

Does spray foam in a metal building have to be covered?

Generally, yes. The IBC (Section 2603.4) and the IRC (R316.4, renumbered R303.4 in 2024) require foam plastic to be separated from the interior by a thermal barrier; in the IRC that's at least half-inch gypsum wallboard or a material meeting NFPA 275. Some intumescent coatings are ICC-ES listed as an alternative, but only over the specific foams and at the thicknesses in their report, such as ESR-3702.

Does bubble foil or a radiant barrier work in a metal building?

Only as an add-on, and only facing an air space. The U.S. Department of Energy says the reflective surface must face an air space of at least 1 inch, and reports 5–10% cooling cost reductions in warm, sunny climates. Radiant barriers don't slow conductive heat flow the way insulation does, and dust reduces their effect.

How much does it cost to insulate a metal building?

HomeGuide (November 2025) puts pole barn and metal building insulation at $1.00–$4.50 per square foot installed: about $2,600–$13,500 for a 30x40 and $4,500–$22,100 for a 40x60. Closed-cell spray foam runs $1.30–$2.90 per board foot. Thermal barriers are often quoted separately. The estimator works out square footage and board feet for your building.

Should insulation come with the building kit or be added later?

Blanket and liner systems are cheapest and best installed during erection, because the roof panels go on over them. Spray foam goes in after the shell is closed in and all roof and wall work is finished, which also avoids re-foaming after later panel repairs.

Can I insulate a metal building myself?

Faced blanket goes in during erection and is a realistic DIY job on a small building. Two-component spray foam needs heated, proportioned equipment, respiratory protection and the right substrate conditions, which is why industry guidance points to installers certified through SPFA's Professional Certification Program.

Does insulation reduce rain noise on a metal roof?

Yes. Johns Manville's faced metal building blanket at R-19 has a noise reduction coefficient of 0.85–0.90 (ASTM C423), and foam bonded to the panel damps its vibration. See does spray foam reduce noise for more.

AT
ArmorThane Technical Team · Springfield, Missouri
Written from manufacturer data sheets, code text and 35+ years of spraying and supporting applicators. Last updated September 26, 2026.

Methodology and sources

Assembly U-factors are ASHRAE 90.1-2016 Appendix A values as reproduced by NAIMA; effective R is 1/U. Energy code values are the 2021/2024 IECC metal building rows as reproduced by Bay Insulation and Thermal Design, and residential values come from PNNL; verify against the code your jurisdiction adopted. Dew points use the Magnus formula (Lawrence 2005), and surface temperatures use air films of R-0.68 inside and R-0.17 outside. Costs are dated third-party estimates. ArmorFoam figures come from ArmorThane product pages and data sheets.

  1. Bay Insulation, codes and standards (IECC 2021/2024 metal building tables): bayinsulation.com/codes-standards/
  2. Thermal Design, 2024 IECC code analysis: thermaldesign.com/techinfo/codeanalysis/
  3. Dalkita, insulation code requirements for metal buildings: dalkita.com/insulation-code-requirements-for-metal-buildings/
  4. Ceco Building Systems, energy code insulation solutions for metal buildings: cecobuildings.com/blog/energy-code-insulation-solutions-metal-building
  5. NAIMA, Guide to Insulating Metal Buildings for Compliance (ASHRAE 90.1-2016 App. A) (PDF): bayinsulation.com/wp-content/uploads/2023/09/NAIMA_ASHRAE_Guide_to_Ins
  6. NAIMA, ASHRAE 90.1 compliance for metal buildings (90.1-2001 values) (PDF): therm-all.com/wp-content/uploads/2018/09/ASHRAE-90.1-Compliance-for-Me
  7. Thermal Design, ASHRAE acknowledges metal building U-factors (2010): thermaldesign.com/techinfo/newsMain/ashrae_acknowledges_metal_building
  8. U.S. DOE, COMcheck: energycodes.gov/comcheck
  9. ICC Digital Codes (IECC, IRC, IBC): codes.iccsafe.org/
  10. PNNL Building America Solution Center, 2009–2021 IECC/IRC minimum insulation: basc.pnnl.gov/information/2009-2021-iecc-and-irc-minimum-insulation-re
  11. ICC-ES ESR-3702, DC315 intumescent coating (PDF): icc-es.org/wp-content/uploads/report-directory/ESR-3702.pdf
  12. Johns Manville, Microlite L metal building insulation data sheet (PDF): jm.com/content/dam/jm/global/en/building-insulation/Files/BI%20Data%20
  13. Insulation4less, fiberglass metal building insulation: insulation4less.com/insulation/fiberglass/fiberglass-metal-building-in
  14. Lamtec, WMP-VR facing data sheet (PDF): lamtec.com/specs/WMP-VR.pdf
  15. Lamtec, WMP-10 facing data sheet (PDF): lamtec.com/specs/WMP-10.pdf
  16. Lamtec, WMP-30 facing data sheet (PDF): lamtec.com/specs/WMP-30.pdf
  17. Lamtec, WMP-50 facing data sheet (PDF): lamtec.com/specs/WMP-50.pdf
  18. Lamtec, Gymguard facing data sheet (PDF): lamtec.com/specs/Gymguard.pdf
  19. Building Science Corporation, BSD-106 Understanding Vapor Barriers: buildingscience.com/documents/digests/bsd-106-understanding-vapor-barr
  20. Nucor Building Systems, roof and wall insulation systems: nucorbuildingsystems.com/products/metal-building-insulation/roof-wall-
  21. Worldwide Steel Buildings, spray foam insulation for metal buildings (Aug. 2026): worldwidesteelbuildings.com/blog/spray-foam-insulation-for-metal-build
  22. Therm-All, a guide to metal building insulation: therm-all.com/a-guide-to-metal-building-insulation/
  23. Retrofoam of Michigan, will spray foam rust metal buildings: retrofoamofmichigan.com/blog/will-spray-foam-rust-metal-buildings
  24. SprayFoamSys, spray foam on metal buildings: sprayfoamsys.com/spray-knowledge/can-you-use-spray-foam-on-metal-build
  25. Rmax, spray foam insulation on metal buildings (Sept. 2023): rmax.com/blog/spray-foam-insulation-on-metal-building
  26. FoamBid, spray foam on metal buildings: the hailstorm dilemma (Oct. 2025): foambid.co/post/spray-foam-on-metal-buildings-the-hailstorm-dilemma
  27. Hansen Pole Buildings, insulating an all-steel building (Feb. 2024): hansenpolebuildings.com/2024/02/insulate-an-all-steel-building/
  28. GreenBuildingAdvisor, insulating a steel building used as a home: greenbuildingadvisor.com/question/insulating-a-steel-building-used-as-
  29. Garage Journal forum, metal building with exposed closed-cell foam: garagejournal.com/forum/threads/metal-building-with-exposed-closed-cel
  30. TractorByNet forum, metal building insulation regrets and likes: tractorbynet.com/forums/threads/metal-building-insulation-regrets-like
  31. ASTM C1029-20, spray-applied rigid cellular polyurethane thermal insulation: store.astm.org/c1029-20.html
  32. Dew point and the Magnus formula (Lawrence 2005): en.wikipedia.org/wiki/Dew_point
  33. ColoradoENERGY, R-value table (air films, board R-values): coloradoenergy.org/procorner/stuff/r-values.htm
  34. Radiative cooling: en.wikipedia.org/wiki/Radiative_cooling
  35. Propane (density and combustion): en.wikipedia.org/wiki/Propane
  36. U.S. DOE Energy Saver, radiant barriers: energy.gov/energysaver/radiant-barriers
  37. ENERGY STAR, seal and insulate: energystar.gov/saveathome/seal_insulate
  38. HomeGuide, pole barn and metal building insulation cost (Nov. 2025): homeguide.com/costs/spray-foam-insulation-cost-pole-barn
  39. HomeGuide, spray foam insulation cost (Dec. 2025): homeguide.com/costs/spray-foam-insulation-cost
  40. MetalPro Buildings, metal building insulation guide (2026): us.metalprobuildings.com/metal-building-insulation-guide-r-values-type
  41. LTH Steel Structures, faced metal building insulation (Sept. 2026): lthsteelstructures.com/shop/products/categories/faced-insulation/
  42. ArmorThane, closed-cell spray foam guide: armorthane.com/closed-cell-spray-foam/
  43. ArmorThane, spray foam R-value guide: armorthane.com/knowledge-center/spray-foam-r-value-guide/
  44. ArmorThane, open-cell spray foam guide: armorthane.com/knowledge-center/open-cell-spray-foam-guide/
  45. ArmorThane, ArmorFoam 0.5 open-cell spray foam: armorthane.com/products/armorfoam-products/open-cell-spray-foam/
  46. ArmorThane, ArmorFoam Roof 200: armorthane.com/products/armorfoam-products/roof-200/

Stop the drip. Keep the heat.

ArmorThane-certified applicators spray closed-cell ArmorFoam on through-fastened steel buildings and put the foam type, thickness, R-value and fire barrier in writing. Contractors, we make the foam, build the rigs and train your crew, with no franchise fee and no royalties.

United States 417-831-5090 · Canada 780-444-6200

CONTACT US

REQUEST A QUOTE OR

BECOME AN APPLICATOR

ArmorThane has built a strong reputation over the past 30 years for producing high-quality, durable protective coatings.

group 115 660555abebfe4
Phone Number

Tel: 417.831.5090

group 115 1 660556c21395c
Email Us

moreinfo@armorthane.com

Step 1 of 3

We want to help you find the best ArmorThane applicator for your protective coating project. Please either fill out the request form below or call us toll free at 417-831-5090, any time Monday-Friday, 8:00 a.m. to 5:00 p.m. Central Standard Time.

RV Find An Applicator

Protective Coating Applications

Products

Applicator Opportunities

Knowledge Center

Galleries